Parallel conductors are found in electrical transmission and distribution systems including large ampacity feeders or loads. However, current unbalance often occurs, especially in alternating current systems. This non-regular current distribution causes overheating and premature aging, facilitating the occurrence of failures. Therefore, a fault diagnosis system is a must, which can be performed by monitoring in real time the individual currents flowing through the conductors. In this paper, a setup, including three parallel aluminum conductors of large cross-section, a spacer, and two terminal substation connectors, is analyzed. A real-time, wireless, coreless, and contactless system based on three low-cost Hall effect sensors is proposed, which is also easy to install. The experimental results, which include 14 cases comprising 13 fault modes and a well-installed set, prove the suitability and potential of the proposed approach since it allows a correct real-time detection of all analyzed faulty conditions as well as the detection of currents exceeding the thermal rating of the conductors.