The aim of this paper is to model the steady-state performance of a vapour-compression liquid heat pump with the use of neural networks. The model uses a generalized radial basis function (GRBF) neural network. Its input vector consists only of parameters that are easily measurable, i.e. the chilled water outlet temperature from the evaporator, the cooling water inlet temperature to the condenser and the evaporator capacity. The model then predicts relevant performance parameters of the heat pump, especially the coefficient of performance (COP). Models are developed for three different refrigerants, namely LPG, R22 and R290. It is found that not every model achieves the same accuracy. Predicted COP values, when LPG or R22 are used as refrigerant, are usually accurate to within 2 per cent, whereas many predictions for R290 deviate more than ±10 per cent.
No takes yet. Share an insight, caveat, or question.
Bechtler et al. (2001) studied this question.