This is the authors' abstract. We don't add key points for this paper.
Power line failures can cause wildfires, particularly in regions like California, Australia, and Portugal. High-wind conditions can lead to the clash of power line conductors, ejecting metal particles that can ignite nearby vegetation. While ignition by particles has been the focus of experiments before, its modelling remains understudied. This paper presents a model to predict ignition by particles, focusing on smouldering as the critical stage before flaming. Particle trajectory and cooling in flight are simulated stochastically using Newtonian equations, while ignition of vegetation is modelled through a pseudo-one-dimensional thermochemical model with Gpyro. Using weather and fuel data from California as a case study, results show that for wind speeds up to 20 m/s, Aluminium particles with a diameter of at least 6.5 mm, ejected from a 20 m high power line, land at temperatures above 740 °C and can ignite grass and shrub fuel beds, creating an at-risk zone of 274 m 2 around the conductor clash point, extending up to 52 m from the power line. Fuel moisture is the primary factor influencing ignition, followed by particle size. This modelling study contributes to close the gap in modelling ignition by particles and offers insights for mitigating wildfire hazards from power lines.
Answers are grounded in this paper and cite their sources.
No takes yet. Share an insight, caveat, or question.
Javaloyes et al. (2025) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: