Answers are grounded in this paper and cite their sources.
It has been known for many years that the grounding resistance of a concentrated electrode drops when it is subjected to a high current charge. This helps reduce the ground potential rise. The degree of the resistance depends on the magnitude of the ionization gradient of the soil E/sub o/. Based on both a theoretical analysis and a critical review of the large number of available measurements, this paper recommends that E/sub o/ be taken equal to 300 kV/m for typical soils. This is significantly less than the 1000 kV/m value used by some authors. Graphs are also given describing the behaviour of the rod electrodes which are used in many field installations.>
No takes yet. Share an insight, caveat, or question.
A.M. Mousa (1994) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: