A 330-kv 1,300-kv BIL air switch has been developed which has been thoroughly tested for radio influence, corona, 60-cycle flashover, impulse flashover, switch gap co-ordination at 1,425 kv basic impulse insulation level (BIL), current capacity, and mechanical ability. Data obtained in this development also proves out the design of a switch using stacks eight insulators high, 1,425 kv BIL. A 330-kv interrupter has been developed capable of interrupting currents, both leading and lagging at very small power factors, of at least 10 amperes.
No takes yet. Share an insight, caveat, or question.
Gross et al. (1954) studied this question.