Condition monitoring of gas insulated high voltage equipment is important to ensure reliable operation of electricity networks. Partial discharge (PD) monitoring is well established for existing SF6equipment, but still in its infancy for the emerging SF6alternatives as the power industry transitions from SF6. PD characteristics of 20% C3F7CN / 80% CO2gas mixture as a viable retrofill solution were extensively investigated over extended energization periods in a busbar demonstrator designed for SF6and rated to 420/550 kV. Protrusions of 3, 5, 10 and 15 mm needle lengths were used on the high voltage conductor for comparative PD investigations of SF6and 20% C3F7CN / 80% CO2gas mixture. PD activity was measured with IEC 60270 (apparent charge) and ultra-high frequency (UHF) detection methods. The PD patterns recorded for all needle lengths were representative of a protrusion-on-conductor defect and the two PD detection methods were comparable. For identical defect lengths, SF6showed a comparatively longer time-to-breakdown when compared to a 20% C3F7CN / 80% CO2mixture. Results obtained in a controlled laboratory environment demonstrate wider applicability to field measurements of C3F7CN based mixtures adopted for retrofill application in SF6-designed gas insulated busbar.