Answers are grounded in this paper and cite their sources.
A single-phase, 230 V Superconducting Fault Current Limiter using two Bi2223 HTS tubes with the total critical current 2.5 kA situated in vacuum insulated cryostat has been described in this paper. We designed and manufactured the inductive SFCL with an open core as core shielded type acquired the optimal design parameters by using Finite Element Method. We tested the limiter performances at liquid nitrogen temperature 77 K. We proved that the performances of properly designed limiter with open core could be comparable to the limiter with closed core.
No takes yet. Share an insight, caveat, or question.
Kozak et al. (2005) studied this question.