Answers are grounded in this paper and cite their sources.
This paper presents the design and testing of a full-scale 330-kV, 210-MVA transformer tank designed to withstand the pressure effects of a 20 MJ, three-cycle low-impedance fault in oil, and fail at its cover in a safe and controlled manner above that amount of energy. The transformer tank, equipped with a mockup active part, was designed for arc resistance using nonlinear static finite-element analysis and a specific rupture criterion. It was then tested using an experimental methodology based on injecting pressurized air into the water-filled tank. To adequately reproduce the effects of an arc in oil, the test parameters were determined using explicit dynamic simulations. The transformer tank performed as predicted by the finite-element and explicit dynamic simulations. The energy levels used in the tests here are, to our knowledge, the largest ever reported. This study demonstrates that it is feasible to design a power transformer to safely withstand high-energy low-impedance faults of short duration.
No takes yet. Share an insight, caveat, or question.
Brodeur et al. (2019) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: