This is the authors' abstract. We don't add key points for this paper.
This paper presents the loss analysis on the saturated iron-core superconducting fault current limiter (SISFCL) for a VSC-HVDC transmission system. The numerical model of SISFCL as well as its loss calculation on superconducting parts were carried out by the finite-element method (FEM) using the H-formulation merged into the commercial package COMSOL. The SISFCL model was established for a practical ±10 kV VSC-HVDC system, and the fault current situation was simulated using the PSCAD with a SISFCL. The capability of fault current limiting was verified using the analysis of electromagnetic characteristics, and the corresponding patterns of magnetic field in the iron-core were studied. During the process of fault current limiting, the instantaneous power losses in the superconducting components were studied with the increasing DC bias current. Even in a DC grid system, results proved there were considerable amounts of losses occurred in the superconducting parts, when the SISFCL encountered the fault currents.
Answers are grounded in this paper and cite their sources.
No takes yet. Share an insight, caveat, or question.
Shen et al. (2021) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: