This is the authors' abstract. We don't add key points for this paper.
The high-voltage direct-current transmission based on voltage source converter (VSC-HVDC) system has pointed the way for the development of the smart grid, yet one challenge to be faced is that VSCs are vulnerable to dc short-circuit faults due to the huge discharge current of the dc-link capacitor. Therefore, the saturated iron-core superconductive fault current limiter (SI-SFCL) is introduced to limit the fault current to a relatively low level. The working principle and electrical properties of the SI-SFCL are discussed first. The relationship between the inductance and dc gird current of the SI-SFCL is deduced. The transient process of a short-circuit fault in the VSC-HVDC system with the SI-SFCL is studied. The maximum current and the drop velocity of dc rail voltage are presented according to the parameter of the SI-SFCL. The effectiveness of the SI-SFCL is proved by comparing fault currents and voltages of the VSC-HVDC system with and without it in PSPICE.
Answers are grounded in this paper and cite their sources.
No takes yet. Share an insight, caveat, or question.
Li et al. (2016) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: