Answers are grounded in this paper and cite their sources.
) in multiple buildings and from different outdoor locations. From the measurements, we are able to estimate the concentration variations indoors for a building operating under "typical" operating conditions. The mean indoor spatial coefficients of variation are 30% to 45% from a daytime outdoor release are around 80% during an outdoor evening release. Having estimates of the spatial coefficient of variation provides stakeholders, including first responders, with the likely range of concentrations in the building when little is known about the building characteristics and operating behavior, such as developing urban-scale hazard and consequence analyses. We show differences in indoor measurements at different distances to the release points, floors of the building, and heating, ventilation, and air conditioning system (HVAC) operation. We also show estimates at different time resolutions. The statistics show that in the studied medium to large commercial buildings, spatial differences would result in peak indoor concentrations in certain parts of the buildings that may be substantially higher than the building average. To our knowledge, very few tracer gas measurements have been conducted in buildings of this scope, particularly with measurements on multiple floors and within a floor. The resulting estimates of spatial variability provide a unique opportunity for hazard assessment, and comparison to multi-zone models.
No takes yet. Share an insight, caveat, or question.
Sohn et al. (2019) studied this question.