Computational modeling study demonstrates accurate, accelerated AC/DC power-flow calculations in hybrid HVDC systems, indicating improved grid-level simulation efficiency.
Conventional quasi-steady-state models treat a self-adaptive STATCOM and line-commutated converter (SLCC) station as an LCC with an external reactive-power source, which cannot fully represent valve-side coupling. This paper develops a three-phase stationary-frame differential model for the SLCC and derives quasi-steady-state expressions for the average DC voltage and fundamental displacement angle. The non-commutation equivalent voltage is decomposed into fundamental and nonfundamental components. The fundamental component is retained in the power-flow model, while a control-informed harmonic extension evaluates the corresponding average DC-voltage correction over the tested operating domain. A positive-sequence fundamental-frequency formulation calculates the commutation overlap angle, and a first-zero diagnostic identifies control-sensitive conditions associated with the fast SVG voltage response. When the fast commutation-direction voltage reaches zero or reverses before current transfer is completed, a control-equivalent effective-area formulation provides an alternative low-order representation. The station equations are incorporated into a sequential AC/DC power-flow algorithm and validated against the engineering PSCAD/EMTDC main-circuit and control model of the Yangzhou–Zhenjiang HVDC Phase II project. Across the stable tested operating points, the phase-aware EMT-derived harmonic DC-voltage correction ranges from 0.585% to 1.245%, remaining below the adopted 2% screening threshold. The control-informed estimate follows the EMT-derived correction, whereas the phase-independent conservative bound reaches 2.128% at high controller gain. Across eight cases with available PSCAD reference values, the control-equivalent formulation reduces the mean and maximum overlap-angle errors from 0.90∘ and 1.37∘ to 0.78∘ and 1.09∘. For the benchmark power-flow cases, the maximum relative errors are 1.3% for the SLCC bridge reactive power and 1.0% for the SVG reactive-power output, and the calculation converges without sustained oscillation. A representative operating-point calculation is completed in approximately 3 s with the quasi-steady-state (QSS) formulation, compared with about 15 min for the engineering EMT benchmark.
No takes yet. Share an insight, caveat, or question.
Li et al. (2026) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: