This is the authors' abstract. We don't add key points for this paper.
The pole-to-ground fault is the most common fault in the true bipolar modular multilevel converter based high voltage direct current (MMCHVDC) grid. The study of a fault current calculation method and characteristics is the theoretical basis for relay protection and fast fault isolation technology of MMCHVDC grid. Considering the mutual inductance coupling between lines, this paper proposes a general fault current calculation method for pole-to-ground faults in MMCHVDC grids. Firstly, considering the influence of AC system on MMC and the mutual inductance coupling between lines, the complex frequency domain equivalent model of the MMCHVDC grid and the simplified model of the remote converter station are studied. Based on the characteristics of the true bipolar MMCHVDC grids, the circuit is analyzed in the complex frequency domain, and an improved node voltage method combined with voltage current relation (VCR) is proposed to calculate the MMCHVDC fault current and obtain the corresponding expression. Finally, the proposed method is validated by comparing its calculation results with the simulation results performed on PSCAD/EMTDC, and the characteristics of the pole-to-ground fault in the MMCHVDC grid are further summarized.
Answers are grounded in this paper and cite their sources.
No takes yet. Share an insight, caveat, or question.
Li et al. (2020) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: