As conventional synchronous generators are progressively replaced by converter-interfaced generation (CIG), power systems experience a significant reduction in inertia, leading to increased frequency stability challenges. The assessment of mitigation strategies requires accurate and scalable benchmark systems capable of representing realistic operating conditions. In this context, this paper presents recent advancements in the development of a benchmark system based on the Northeast (NE) Subsystem of the Brazilian Interconnected Power System (BIPS). Developed within the IEEE PES PSPD Task Force on Benchmark Networks for Low-Inertia Systems , the proposed model reflects the operational complexities of a region with high penetration of CIG and enables detailed analysis and validation of frequency stability control strategies. Hence, a comparative study is conducted on potential solutions, including the use of synchronous condensers (SynCons), synthetic inertial control (SIC) in wind generators, and battery energy storage systems (BESSs) equipped with primary frequency control (PFC). Results show that combining these strategies provides the most effective approach to mitigating frequency stability issues in the proposed benchmark system.