A 1 MVA single phase high temperature superconducting (HTS) transformer was manufactured and tested. The rated voltage of primary and secondary of HTS transformer are 22.9 kV and 6.6 kV respectively. BSCCO-2223 HTS tape was used for HTS windings of 1 MVA HTS transformer. In order to reduce AC loss generated in the HTS winding, the concentrically arranged winding was adopted to 1 MVA HTS transformer. Single HTS tape for primary windings and 4 parallel HTS tapes for secondary windings were used considering the each rated current of the HTS transformer. A core of HTS transformer was fabricated as a shell type core made of laminated silicon steel plate. And a GFRP cryostat with a room temperature bore was also manufactured. The characteristic tests such as no load test, short circuit test and several insulation tests were performed at 65 K using sub-cooled liquid nitrogen. Through these test results, the validity of design of HTS transformer was ascertained.