In order to attain reduction in insulation test voltages, voltage-time (V-t) characteristics under AC voltage and voltage-number (V-N) characteristics under lightning impulse and switching impulse voltages were experimentally investigated on the turn-to-turn insulation model, section-to-section insulation model and barrier-oil-duct insulation model of core- and shell-type transformers in EHV and UHV Classes. First, V-t characteristics for AC voltage were obtained in a short time range of a few tens of milliseconds to a long time range of three to four months. The n-values (inclination) of V-t characteristics are distributed around 40 for the short time and several hundreds for the long time characteristics. These values are of essence in determining the AC withstand voltage test. Next, V-N characteristics for both lightning and switching impulse voltages were acquired for up to 1,000 times of application. The n-values (inclination) of V-N characteristics are in most cases distributed around 70 for both impulse waveforms and about 40 in only turn-to-turn insulation models This result will be useful for evaluating the effect of frequent surges on apparatus insulation. Finally, insulation coordination studies were performed based on these experimental results.