This study examines the failure of insulation coordination between insulator strings and external gap line arresters on 35 kV transmission lines during heavy rainfall. Artificial lightning-rain flashover tests were performed in accordance with IEC standards to evaluate their coordination margin. Based on these findings, a method for enhancing the coordination margin is proposed, and its effectiveness is validated through experimental and simulation analyses. The results indicate that the lightning withstand levels of both components decrease with increasing rainfall intensity and rainwater conductivity, and the index of rainwater conductivity of insulator strings is 5.3 times than arrester. At rainwater conductivity of 3000μS/cm and rainfall intensities ranging from 3 to 12 mm/min, the coordination margin fails to meet IEC standards. The lightning arc propagation speed of the arrester under rainfall increases exponentially with rainfall intensity, with a peak increase of 59.5%. Additionally, the arc velocity difference between the gap and the insulation section exceeds 23.1%, which adversely affects operational responsiveness. To address this issue, an induced discharge needle regulation method is proposed. A 10 mm needle reduces the arrester’s breakdown voltage by 19 kV, enabling full-process dynamic control of the arc path, as validated through power-frequency wet withstand voltage tests.