This is the authors' abstract. We don't add key points for this paper.
In Part I of this two-part paper, a power-management and a control strategy for the microgrid autonomous mode of operation were presented. The strategy consists of 1) open-loop frequency control of the system and synchronization of DER units based on a GPS signal; 2) voltage reference setpoint determination for the DER units by the central power-management system; and 3) tracking the assigned setpoints and rejecting disturbances by robust, decentralized, local controllers of DER units. This Part II paper applies the envisioned strategy to a three-DER microgrid. Offline digital time-domain simulation studies in the EMTDC/PSCAD software environment demonstrate the robustness of the local controllers to parametric, topological, and unmodelled uncertainties of the microgrid, its fast performance in tracking the setpoints with zero steady-state error, and rapid disturbance rejection. The results also show the effectiveness of the proposed power-management system in achieving prescribed load sharing of DER units. The digitized algorithms of the proposed control system of the three-DER microgrid are also implemented in NI-cRIO industrial-grade platforms and tested in an RTDS-based real-time hardware-in-the-loop (HIL) environment to demonstrate the feasibility of the strategy for hardware implementation and hardware-based performance validation.
Answers are grounded in this paper and cite their sources.
No takes yet. Share an insight, caveat, or question.
Davison et al. (2012) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: