Energy performance certificates (EPCs) are the principal instrument for assessing and communicating building energy performance in Europe, yet studies testing EPCs against measured energy compare, almost without exception, whole-building totals. This study examines what that practice conceals. In a census of ten recently completed municipal buildings in Sandnes, Norway, every floor area, meter scope, and calculation basis was verified against primary sources, and EPC-calculated and measured delivered energy were compared at three levels of data resolution: whole-building for all ten buildings, energy-carrier for one, and end-use for one. Measured energy exceeded the calculation in eight of ten buildings; the portfolio-mean deviation is +28% (range − 8% to +102%). At end-use level, a building with an unremarkable aggregate deviation of +17% (net energy) deviated by −38% to +110% on its individual end uses, opposing errors cancelling at the meter. A cancellation index, C = 1 − |Δ|/D, quantifies the effect: C = 0.66, two-thirds of the deviation magnitude invisible in the whole-building total. A verified floor-area error alone would otherwise have made the same building appear compliant. Whole-building agreement is therefore not evidence that a building performs as calculated. Certificate validation needs the end-use resolution that building performance evaluation has long applied to diagnosis, and the study shows the cost of proceeding without it.