Answers are grounded in this paper and cite their sources.
This paper proposes a novel wavelet-transform-based directional algorithm for busbar protection. The algorithm decomposes the current and voltage signals into their first-level details, which consist of frequencies in 500- to 1000-Hz bandwidth, for generating directional signals. A high level of computational efficiency is achieved compared to the other wavelet-transform-based algorithms proposed, since only the high-frequency details at the first level are employed in this algorithm. The validity of this method was exhaustively tested by simulating various types of faults on a substation modeled in the alternative transients program/electromagnetic transients program. The algorithm correctly discriminated between bus faults, various types of external faults, and transformer energization even in the presence of current-transformer saturation. This paper also provides the design details of the algorithm using field-programmable gate array technology.
No takes yet. Share an insight, caveat, or question.
Valsan et al. (2007) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: