Seismic performance and structural safety of facilities shall be comprehensively considered in substation foundation design to maintain safe operation of substation facilities under seismic loading. A novel foam-sandwich-panel-based horizontal vibration isolation technology is proposed in this study to improve the horizontal seismic resistance of substation foundations. To investigate the vibration isolation response of substation foundations subjected to horizontal seismic excitation, a series of model tests were performed to assess the isolation performance of the vibration isolation system under different excitation frequencies. The influences of geometric design parameters of the foam sandwich-panel isolation structure on the vibration isolation effectiveness of the substation foundation were also examined. Test results reveal that the foam sandwich-panel isolation system achieves favorable horizontal vibration isolation performance over the entire excitation frequency range. Appropriate arrangement of foam sandwich panels can substantially reduce the foundation’s horizontal vibration response. The influence of panel thickness on isolation effectiveness varies with excitation frequency. Raising the elastic layer thickness of the sandwich panel, the width of the isolation surface, and the coverage range further improves the vibration isolation performance of the system.