A current-limiting device (CLD) on a 400 Hz shipboard bus protects its load by turning an IGBT path off and diverting the current into a reactor. An IGBT that has failed stuck-on keeps supplying the load and appears healthy, so the loss of turn-off capability can be found only by testing the path in service, without creating a fault current and with the single Hall sensor already installed. This paper designs and validates such a self-test. Short high-impedance pulses at 45° and 225° force a current-path transfer in each of the two anti-series IGBTs, whose transient current drop ratio is the decision metric; a three-of-four criterion and a current-dependent deferral rule confine verdicts to currents the measurement chain can resolve. On production units, no healthy resistive-load capture failed at or above 7.5 A (0 of 25), and all three captures with a jumper emulating a both-device stuck-on fault failed. Fault cases above 10 A, where hardware injection was impossible, are evaluated in a chain model calibrated on healthy captures. A closed-form rule relating the lowest diagnosable current to the sampling period, sensor sensitivity and noise reproduces the measured 7.5 A limit and indicates how the test transfers to other hardware.