Answers are grounded in this paper and cite their sources.
Residential electric-vehicle (EV) charging overloads low-voltage feeders and injects harmonic currents; an active harmonic filter (AHF) must be sized for the worst harmonic current, which depends on when vehicles charge. We treat the charging schedule as a design variable of the AHF. A central four-leg AHF is sized in closed form to IEEE 519–2022 inside every evaluation of a fleet-scheduling objective, the fleet is dispatched through 72 aggregator signals that guarantee every user’s departure state of charge, and all schedules are validated with one-minute and harmonic power flows on all 2718 nodes of the IEEE European LV test feeder. Coordinated charging removed all voltage, unbalance and thermal violations, reduced peak demand by 45% and losses by 48%, and raised the charger emission level at which IEEE 519 is exceeded from 3.0 to 6.8 times the measured spectrum, cutting the required AHF rating by 71% at twelve times. Four metaheuristics did not improve on rule-based valley filling, harmonic-aware and harmonic-blind schedules coincided, and vehicle-to-grid lowered the hourly objective only when battery throughput was weighted below 0.08–0.14, without network benefit at one-minute resolution. With non-linear household loads the households dominated the distortion and no filter was needed for any schedule.
No takes yet. Share an insight, caveat, or question.
Aslan et al. (2026) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: