Radon, a radioactive indoor pollutant with a linear no-threshold lung-cancer link, has a building performance obligation of 100–300 Bq/m3.This systematic review, conducted in accordance with the PRISMA 2020 guidelines, screened 253 records and synthesised 103 references (94 studies plus 9 additional records). Geology establishes potential source strength; in the cases reviewed, at comparable source strength, air renewal was the dominant controllable determinant. Heat-recovery ventilation reduced radon by a median of 39%; sub-slab depressurisation exceeded 85% in a high-concentration pilot yet left 662 and 328 Bq/m3 above the 300 Bq/m3 reference level; and a barrier reduced radon by about 90%, but residuals remained above recommendations. Radon-controlled prototypes achieved 86% reductions at 34% fan runtime, from 8000 to 800 Bq/m3; infiltration-reducing retrofits were associated with 32–67% increases. Low-cost monitors showed 20–50% errors below 200 Bq/m3 (3–5% for the best field units). Within the screened literature, no peer-reviewed model-predictive or reinforcement-learning study with radon in its objective was identified; digital-twin indoor-environmental-quality frameworks omit radon. Alicante campaigns (2–22 days, passive detectors) indicate the conditions measured, not average annual exposure, without independent ≥1-season corroboration. Radon is a conditional tracer of air renewal, not a CO2, VOC or PM proxy. A decision hierarchy, a measure–model–mitigate–control framework and six gaps are proposed.