Answers are grounded in this paper and cite their sources.
This study presents the experimental determination of the liquid-phase heat transfer coefficient and the gas-phase mass transfer coefficient ratio ( h L a/K y a ) based on Merkel's model. Experiments were conducted in a pilot-scale humidification tower packed with 8 mm × 8 mm Dixon rings and operated with both ambient and saturated air. The analysis shows that energy and moisture transfer are concentrated in the upper sections of the tower. Surface energy losses accounted for only 2% of the total transferred energy and were therefore neglected in subsequent calculations. Mean deviations of temperature between experimental and predicted air outlet conditions are 0.65 °C for ambient air to 6.62 °C for saturated air. Overall tower efficiencies ranged from 89 to 95% with ambient air and 96–99% with saturated air. The results contribute new experimental data for this packing configuration and support future design and optimization studies for humidification systems.
No takes yet. Share an insight, caveat, or question.
Reyes et al. (2026) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: