In electric power system protection, selectivity ensures that only the smallest possible section of the grid where a fault occurs is isolated, minimizing disruption to the overall network. This paper presents the enhanced Automated Protection system Verification (APV) tool, which provides a mathematically rigorous framework for verifying protection system selectivity in critical power systems. The tool leverages formal verification, specifically Timed Automatons and the Uppaal model checker, to exhaustively evaluate all admissible single-fault scenarios within one automated verification workflow and detect misconfigured circuit breakers (CBs), unlike simulation-based methods which simulate one fault per run. The enhanced version extends support from radial to multi-source (open or closed) ring networks and incorporates additional selectivity schemes, including directional, zone, and directional-zone. The key contributions of this work are new Timed Automatons (TAs) models for directional (D), zone (Z), and directional-zone (DZ) selectivity, the extension of the verification framework to multi-source open-ring and closed-ring topologies, and current estimation functions that enable formal verification of these ring networks. Validation across diverse network configurations demonstrates the tool’s correctness, scalability, and efficiency, confirming that it offers a practical and robust solution for verifying protection system selectivity in critical power systems such as shipboard networks.