Answers are grounded in this paper and cite their sources.
High-voltage direct current (HVDC) transmission systems are an essential technology for long-distance bulk power transmission, and their reliable protection is crucial. A novel application of the Time Domain Decomposition (TDD) method is presented in this paper for the analysis of electrical transients in HVDC systems. Extracted characteristic “electrical mode shapes” from synchronized terminal measurements serve as a unique, sign-consistent spatial fingerprint for fault identification. Fault detection is achieved using an effective Z-score-based adaptive thresholding method applied to modal energy. Based on the mode shapes, feature vectors are extracted to train various machine learning classifiers, along with the sign-consistency enforcement method. Fault type classification is performed using a Support Vector Machine (SVM). At the same time, a regression tree model is employed to locate faults across a wide range of simulated fault types, fault resistances, and fault locations in a model HVDC system. The simulation results for the two-terminal VSC HVDC scheme show that the proposed TDD-based method provides a common platform for fault detection, classification, and location identification. The proposed method achieves 94.1% classification accuracy, a fault location MAE of 0.50 km, and a fault resistance estimation MAE of 2.6 Ω. A 5-fold Cross-Validation (CV) process conducted over an expanded dataset demonstrates the reproducibility of the proposed approach.
No takes yet. Share an insight, caveat, or question.
Zafari et al. (2026) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: