This experiment aimed to investigate the performance of nanocellulose-enhanced short-chain fluorocarbon foam extinguishing agents on gasoline pool fires under different operating conditions. The performance and influencing factors of gasoline pool fire extinguishing were revealed through changing the ethanol ratio, wind speed, and foam application conditions. The dynamic distribution and evolution of the flame temperature field throughout the entire process were captured using an infrared thermal imager. Based on this, the influence mechanism of extinguishing agents on the fire extinguishing performance was analyzed from a physicochemical perspective. The results indicated that the application of extinguishing agents resulted in the flame height to increase sharply. With the increase in ethanol ratio from 10% to 30%, the maximum flame height and extinguishing time gradually decreased, with the extinguishing time shortening from 32 s to 13 s. Meanwhile, the maximum flame temperature also decreased from 942°C to 900°C. With the wind speed increasing from 2.5 m/s to 3.5 m/s, the fire extinguishing time decreased from 26 s to 16 s, and the maximum flame temperature dropped from 924°C to 888°C. Compared to the slow application, the fire extinguishing time under robust application was shorter, and the maximum flame temperature was higher. The results could provide guidance for the efficient extinguishing of gasoline pool fires while supporting the development of energy safety.