Converter current and power limits alter the fault voltage–current relationship in microgrids. This paper coordinates a bounded voltage-dependent pickup characteristic with mode-specific setting groups for passive laterals and their immediate backups. A common balanced static source model is used for pre-fault, fault, and post-clearance calculations. An outer differential-evolution search determines pickup parameters, monotone propagation solves the fixed-pickup timing inequalities, and an independent linear program checks selected timing solutions. The 10 kV, 14-bus study includes 450 setting faults and 210 validation faults, with 280 prescribed validation events. Under the same two-group configuration and a 40 ms trip-command floor, voltage supervision with separate joint retuning reduces islanded target-pair TROT by 30.11% over 30 bus-14 faults and by 10.30% over all 70 bus-14 target faults relative to IDMT. The mean main-protection trip-command delay over all 210 validation faults decreases from 49.743 to 48.584 ms (2.33%). All prescribed validation events pass the proposed-setting checks, with a minimum worst-case CTI of 300.078 ms and a minimum error-adjusted normal pickup margin of 1.25101. Nine design-parameter combinations use twenty seeds per group and the same selection rule as the principal benchmark. The grouping provides mode-specific setting management; no incremental clustering benefit or quantified single-to-two-group improvement is established. Conclusions apply to the finite balanced static libraries, fixed source ratings and internal topology, and correct pre-fault group selection.
No takes yet. Share an insight, caveat, or question.
Zhang et al. (2026) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: