Wastewater generated during transformer fires may contain both transformer oil and firefighting foam, forming stable emulsions that are difficult to treat. This study investigated the treatment of simulated transformer oil wastewater by magnetic coagulation under foam-free and foam-containing conditions. The effects of polyaluminum chloride (PAC) dosage, polyacrylamide (PAM) dosage, pH, and magnetic powder dosage on oil removal were examined. The results showed that the preferred conditions differed between the two systems. For the foam-free system, an oil removal efficiency of 96.61% was achieved with 400 mg/L PAC, 8 mg/L PAM, a pH of 7, and 60 mg/L magnetic powder, at a magnetic field strength of 120 mT and a settling time of 15 min. For the foam-containing system, an oil removal efficiency of 94.79% was achieved with 500 mg/L PAC, 10 mg/L PAM, pH 8, and 80 mg/L magnetic powder under the same magnetic field strength and settling time. Zeta potential analysis indicated that the addition of firefighting foam affected the surface charge of the emulsion system. Overall, firefighting foam increased the required coagulant dosage and slightly reduced oil removal efficiency. Magnetic coagulation nevertheless achieved effective oil removal in both systems, showing potential for treating transformer oil wastewater containing firefighting foam.