Answers are grounded in this paper and cite their sources.
As renewable energy penetration continues to increase, converter control dynamics play a critical role in power system synchronization, making small-signal synchronization stability an important concern in converter-dominated power systems. Grid-following (GFL) and grid-forming (GFM) converters differ in synchronization mechanisms and stability characteristics, and their coordinated operation may introduce complex dynamic interactions. These differences and interactions make it challenging to clarify how converter control dynamics affect synchronization stability, both individually and through their interaction. This paper develops a unified small-signal modeling and path decomposition method (PDM) for GFL and GFM converters in single- and two-converter systems. Based on this, a stability contribution index is introduced to quantify and compare the effect of each path on the dominant oscillatory mode. The proposed method separates the effects of AC network, single converter, and inter-converter interaction paths and reveals how key control parameters affect system stability, thereby providing a theoretical basis for stability assessment and coordinated parameter design in multi-converter systems.
No takes yet. Share an insight, caveat, or question.
Li et al. (2026) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: