This study developed a LabVIEW-based monitoring framework for a Power Pallet PP20 downdraft biomass gasifier. REVIOGA displays serial data from the existing Arduino-based Process Control Unit (PCU), while ANAPAGA visualizes CSV records stored by the PCU. The contribution is an application-specific combination of live supervision and retrospective visualization using the existing controller. Two distinct signal paths were considered: a laboratory path from a Fluke 5500A through an NI USB-6009 to REVIOGA, and an operational path from installed sensors through the PCU and its serial link. Previously reported laboratory mean absolute errors of 0.12 °C and 0.03 psi and a mean graphical response interval of 220 ms lack the point-level records and timing statistics needed for independent assessment and are treated as provisional descriptive values. One 40 min operational demonstration showed no observed interface freezing or memory overflow. Data integrity was not independently measured. Legacy ANAPAGA screenshots demonstrate plotting functionality, but their time base and pressure conversion remain unresolved; they are not quantitative validation of process conditions. The framework therefore provides a proof of concept for PP20 monitoring and visualization. Reproducible measurement validation, verified message documentation, source-code release, and repeated operational tests remain necessary before accuracy or reliability claims can be established.