This study addresses the challenge of meeting the continuous cooling demands of data centers using an inherently intermittent solar-powered cooling system. To overcome weather dependency, the developed system integrates thermal energy storage with phase change materials to ensure a consistent thermal supply during non-solar hours. The proposed numerical model is validated against experimental data, demonstrating high reliability with a maximum relative error of less than 10% (a minor deviation of approximately 2°C). The system's performance is comprehensively evaluated through energy, exergy, and exergoeconomic analyses across three major Canadian cities: Vancouver, Toronto, and Montreal. The numerical results indicate that Montreal consistently exhibits the highest exergetic efficiency, reaching a maximum of 20.6%, although it incurs the highest overall cost. Conversely, Toronto proves to be the most economically viable location, achieving the lowest total cost rate of approximately 40.0 $/h. Furthermore, the thermodynamic evaluation demonstrates a highly favorable maximum coefficient of performance of 0.817 for the integrated system, depending on the selected operating temperatures.