Residential ground-source heat pumps enter energy planning with a default seasonal performance factor of 3.5 and a thin field record. Two family houses in Samobor, Croatia, have a simple configuration: one borehole of 200 m (House A) or 100 m (House B) with a single-U collector, an inverter unit connected directly to dense underfloor circuits without buffer tank or backup heater, domestic hot water at low compressor speed and passive floor cooling. The paper reports 60 and 38 months of metered heat, electricity and seasonal COP, two years of 10-min borehole and supply temperatures, a thermal response test and the open-source modelling chain GEODROID BHEx. The integrated meters give a cumulative seasonal COP of 6.71 and 6.97, the manufacturer's map 6.4 and 5.6 as lower bounds, and the whole-system value with both circulators is 5.6–6.1, above published field-trial means. The model reproduces the held-out 2025 borehole temperatures within −0.4 K (House A) and + 0.6 K (House B, uncalibrated) and agrees with a finite-element model within 0.2 K. A supply 5 K higher reduces the modelled seasonal COP by about 10%, a ground conductivity of 1.8 instead of 2.3 W/(m K) by 3–4%: the result is attributed to the design. Over 25 years the coldest-month source temperature stays at 7.0 and 6.7 °C, passive cooling reaches an electricity ratio of 20–35, and the systems use 38–48% less electricity than an air-source unit. Software and data are on Zenodo.