The interaction between voltage depression and rotor-angle acceleration presents a challenge for heavily loaded transmission systems. This study evaluated an adaptive neuro-fuzzy inference system (ANFIS) controller for a static var compensator (SVC) using a MATLAB/Simulink representation of a 330 kV, 250 km transmission corridor. The ANFIS used voltage deviation and its rate of change to produce a susceptance command and was compared with an uncompensated network, a particle-swarm-optimised proportional–integral (PI) SVC and an artificial neural network (ANN) SVC. For the simulated three-phase fault, the ANFIS case exhibited a voltage-dip depth of 0.22 p.u., a voltage recovery-time indicator of 0.8 s, a first-swing rotor-angle excursion of 46°, and a damping ratio of 0.31. Reported critical clearing times were 0.145, 0.195, 0.235 and 0.265 s for the uncompensated, PI, ANN and ANFIS configurations, respectively. At a 0.200 s clearing time, this corresponds to positive clearing margins for ANN and ANFIS control and negative margins for the uncompensated and PI configurations. The results demonstrate the potential of neuro-fuzzy SVC control to improve the voltage and angular-stability indicators examined in the modelled transmission corridor.