Grid-following (GFL) inverters lose small-signal stability when the grid is very weak, and adding grid-forming (GFM) capacity is a recognised remedy. How much GFM capacity a plant needs, and which parameters decide it, is still hard to answer. This paper studies a GFL inverter and a GFM inverter that share one point of common coupling and export rated power into a grid whose short-circuit ratio (SCR) ranges from 1.05 to 3. A 17-state model includes the phase-locked loop (PLL), current control with voltage feedforward, a virtual-synchronous-machine GFM with Q–V droop, the PCC capacitor and the grid R–L dynamics. Eigenvalue scans over the SCR and the GFM share 𝛾 of the total rating are compared with a simple equivalent-SCR rule, SCR+𝛾/𝑥𝑣 1−𝛾 = SCR𝑐, where 𝑥𝑣 is the GFM reactance and SCR𝑐 the critical SCR of the GFL plant alone. With a 40-Hz PLL the GFL plant alone needs an SCR of at least 2.13, and the GFM share needed at an SCR of 1.2 is 10.2% (rule: 10.6%). Over 22 parameter cases the rule stayed within 0.011 of the full-model share, and it erred on the safe side in 38 of 44 comparisons. GFM inertia, damping and Q–V droop changed the needed share by less than 0.001. Time-domain runs matched the predicted oscillation frequencies within 2.1% and the growth or decay rates within 8%. After a drop from SCR 2.5 to 1.2, the plant stayed stable with 𝛾 = 0.15 but not with 𝛾 = 0.05.