ABSTRACT High outdoor‐air (OA) ventilation improves infection control but can sharply increase HVAC energy use in hot–dry climates. This study designs and optimizes a sealed, U‐shaped internal‐condenser heat‐pipe heat exchanger (HPHE) that thermally couples exhaust and supply ducts without air mixing. A hybrid porous/ ε –NTU screen is used to identify a practical operating band of 2.0–2.5 m·s⁻¹ (Δ T ≈ 20 K) for penalty‐aware operation. Transient two‐phase VOF simulations map loop stability versus condenser length and working‐fluid fill ratio, rejecting 300 mm legs due to flooding and selecting a 150 mm U‐leg at FR ≈ 50% in a laminar, capillary‐dominated regime. Conjugate CFD at the selected operating conditions predicts a ≈ 15.6 K reduction in hot‐duct outlet temperature and an ≈8.4 K increase in supply‐duct outlet temperature, with only watts–tens of watts of added fan power; the loop pumping requirement is O (10⁻² W). Verification and validation follow AHRI Guideline V conventions, including three‐level mesh/time refinement (GCI₉₅% < 5%), two‐phase energy‐balance checks, and cross‐study comparisons ( ε–v and ) against recent HPHE literature (2021–2024). At the nominal point, the recovered sensible heat is = 1.621 kW with ±1 σ = 0.064 kW (4.0%) and a 95% confidence interval of 1.497, 1.748 kW (±7.8%). The results establish a compact, stable HPHE module that delivers strong, net positive heat recovery for high‐ventilation, infection‐control HVAC operation in extreme hot–dry climates.
Mahdi et al. (Sat,) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: