Answers are grounded in this paper and cite their sources.
Analysis demonstrates the impact of soil-structure interaction on seismic response in a stack-type exhaust tower, suggesting implications for structural design.
SSI has a very significant impact on the seismic response of structures. This article uses a certain nuclear safety grade steel stack-type exhaust tower as a basis and compares the effects of considering soil-structure interaction on the seismic response of structures using numerical analysis methods. Through the comparison of floor response spectra of SASSI models with rigid connections of soils with different shear wave velocities, it is known that the floor response spectra of different soils mainly manifest in peak changes, and the shapes of the response spectra are basically consistent. This mainly indicates that the shape of the floor response spectrum of the stack-type exhaust tower structure is mainly related to the characteristics of the structure itself and is not particularly sensitive to the differences in the foundation. The influence of soil-structure interaction on structural response, for the X and Y directions, changes in shear wave velocities are sensitive to the structural response across the entire frequency range; for the Z direction, the influence of soft soil on the structure is mainly reflected in the low-frequency and high-frequency parts.
No takes yet. Share an insight, caveat, or question.
Xue et al. (2026) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: