Using a high-temperature superconductor, we constructed and tested a model superconducting fault current limiter (SFCL). The superconductor and the vacuum interrupter as the commutation switch were connected in parallel using a bypass coil. When the fault current flows in this equipment, the superconductor is quenched and the current is transferred to the parallel coil because of the voltage drop in the superconductor. This large current in the parallel coil actuates the magnetic repulsion mechanism of the vacuum interrupter. Due to the opening of the vacuum interrupter, the current in the superconductor is broken. By using this equipment, the current flow time in the superconductor can be easily minimized. On the other hand, the fault current is also easily limited by large reactance of the parallel coil