In This Paper, A New Protection Scheme In The Areas Of Accurate Fault Detection, Classification And Location Estimation For Multi Terminal Transmission System Compensated With Statcom Is Proposed. The Fault Indices Of All The Phases At All The Terminals Are Obtained By Analyzing The Detail Coefficients Of Current Signals Through Bior 1.5 Mother Wavelet. The Complete Digital Simulation Of A Transmission System With Statcom Is Performed Using Matlab /Simulink For Fault Detection, Classification, And Faulty Terminal Identification With Variations In Fault Distance And Fault Inception Angle For All Types Of Faults And Fuzzy Inference System Is Used To Estimate The Fault Location. The Protection Scheme Yielded Accurate Results Within Half Cycle And Show That The Above Scheme Is Suitable For Multi Terminal Transmission System With And Without Statcom Compensation.
No takes yet. Share an insight, caveat, or question.
J et al. (2016) studied this question.
Synapse has enriched 5 related papers. Consider them for comparative context: