Answers are grounded in this paper and cite their sources.
This report details an investigation of a significant increase in nosocomial gramnegative bacteremia caused by enteric bacilli and Pseudomonas aeruginosa. The chute-hydropulping waste disposal system was identified as a bacteria-rich reservoir, with 108 enteric bacilli and P. aeruginosa per gram of pulp. The system was found to be a gross source of airborne fecal flora. Airborne dissemination of a virus by that system was documented, and other viruses and infective agents of human disease might have been introduced from the waste pulp through the 16-story chute into the patients' ecosystem. Closure of the waste disposal complex resulted in disappearance of enteric organisms and P. aeruginosa from the hospital air. Average colony counts declined from > 150 to 40 per cubic foot of air. The incidence of nosocomial septicemia caused by P. aeruginosa and other gramnegative organisms declined concomitantly and continued at a reduced rate throughout a 19-month follow-up. Even though the evidence is circumstantial, it is urged that hospital designers prevent the described sources of gross contamination and nosocomial hazards.
No takes yet. Share an insight, caveat, or question.
Grieble et al. (1974) studied this question.