Answers are grounded in this paper and cite their sources.
Lightning-induced backflashovers pose significant risks to high-voltage transmission systems, particularly in high lightning activity regions. Conventional backflashover rate (BFR) estimation methods rely on simplified empirical formulas that lack accuracy in complex scenarios. This paper presents a comprehensive simulation framework integrating (i) a Simulation-Based Leader Progression Model (SB-LPM) implemented in COMSOL Multiphysics–MATLAB to evaluate lightning attachment through detailed electrostatic field analysis and streamer-leader dynamics, (ii) ATP-EMTP electromagnetic transient simulations incorporating multi-component Heidler function current waveforms, calibrated to regional lightning measurements, and (iii) a Monte Carlo analysis for statistical assessment of backflashover susceptibility. Applied to a representative 138 kV transmission line in Minas Gerais, Brazil, the framework shows that BFR results are highly sensitive to tower-footing impedance and attachment model selection. The SB-LPM yields systematically different predictions compared to traditional electrogeometric models, yielding approximately 10% lower BFR estimates at 20 Ω grounding impedance relative to the widely used Eriksson model. The framework enables comprehensive lightning performance assessment by incorporating geometry-sensitive attachment modeling, realistic current waveform synthesis, and detailed system transient response, providing valuable insights for transmission line insulation coordination studies.
No takes yet. Share an insight, caveat, or question.
Lobato et al. (2025) studied this question.