This study compared the particle removal performance of an existing general exhaust system with a newly installed local exhaust system in a hospital endoscopy room. Overall, the local system reduced particle concentrations by 56%, showing greater effectiveness for smaller particles. For 0.3 µm particles, reductions during procedures such as Bronchoscopy, Esophagogastroduodenoscopy, and Upper endoscopy reached 70%, 73%, and 78%, respectively. The local exhaust system demonstrated superior particle control and showed potential to reduce the risk of infection in the evaluated environment.