Answers are grounded in this paper and cite their sources.
The presence of moisture in the insulation of power transformers accelerates the degradation of both paper and oil, thereby increasing the risk of unexpected failures. Due to the hygroscopic nature of cellulose, the insulation can retain up to 8% moisture after the transformer manufacturing process. Reducing this moisture content is crucial in extending the operational lifespan of transformers. The drying cycle of paper insulation is a critical step in power transformer manufacturing, directly influencing the insulation’s longevity and overall performance. This paper introduces a nomogram that combines degradation and drying models, enabling the precise optimization of the drying process based on various parameters such as the temperature, paper mass, and extraction rate. The results of this study demonstrate that for a given extraction rate threshold, the required drying time can be determined based on the mass of paper to be dried, the drying temperature, and the degree of paper degradation (degree of polymerization). These predictive tools are essential for engineers and researchers aiming to enhance transformer reliability.
No takes yet. Share an insight, caveat, or question.
Brahami et al. (2025) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: