Simulation study reveals a 209 kWh state-inheritance error in photovoltaic shading scheduling, indicating rolling horizon control balances net energy and louver movement.
Hourly angle optimization for photovoltaic (PV) shading is conducted by selecting values from independent fixed-angle simulations, although the selected hours do not share a consistent building thermal history. This study develops a database-based constant-action rolling horizon look-ahead heuristic that minimizes net electricity for a PV louver in a Beijing office while correcting thermal-history inconsistency. Nineteen angles from 0° to 90° were simulated to construct hourly thermal and PV maps. Schedules were generated for horizons of 1–48 h under a 10° h−1 movement limit and evaluated by continuous EnergyPlus replay. The independently optimized sequence predicted −310.90 kWh of annual net energy, whereas continuous replay yielded −101.61 kWh, revealing a 209.29 kWh state-inheritance error dominated by HVAC electricity. The 12 h horizon minimized net energy at −119.11 kWh. A 24 h horizon incurred a 5.89 kWh penalty while reducing angle changes and total rotation by approximately 65%, indicating a favorable energy–movement compromise. Requiring an angle of at least 15° during occupancy eliminated full closure at a net-energy cost of 35.79 kWh. Continuous replay and operating constraints are therefore necessary when translating fixed-angle databases into implementable façade controls.