Answers are grounded in this paper and cite their sources.
In this study, cooling experiments were conducted using a full-scale experimental house to evaluate the effectiveness of reducing the number of buried rainwater tanks in a hybrid heat-source system from five to four. The following findings were obtained: 1) Raising the tank switching temperature from 24℃ to 26℃ allowed the system to operate continuously for over ten days with four tanks. 2) When comparing periods with similar daily mean outdoor temperatures, the hybrid heat-source system consumed about 4.4% less energy than the air-source system. 3) The system’s energy-saving performance improved as the daily mean outdoor temperature increased.
No takes yet. Share an insight, caveat, or question.
FURUTA et al. (2026) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: