This study evaluates the energy performance of a nominal 1,650 Wp solar photovoltaic (PV) system installed to support lighting on the seventh floor of the Universitas Pamulang parking building and connected to the PLN grid through an Automatic Transfer Switch (ATS). Measurements were recorded every 30 minutes from 09:00 to 20:00 Western Indonesian Time over seven days, covering voltage, current, power, energy, and battery state of charge. The summary data report an average PV output power of 351.714 W, while average PLN power on days with an active lighting load was approximately 1,508.990 W. The daily PV energy values listed in the tables range from 0.237 to 0.460 kWh, averaging 0.342 kWh. However, these energy summaries cannot be consistently reconstructed from the full interval data and are therefore not used to quantify PLN energy reduction. A single comparison between the KWS-302 monitor and an AVO meter gives relative differences of approximately 0.88% for voltage and 17.89% for current; current-measurement accuracy is consequently not considered validated. Design calculations indicate a 1,350 W lighting load requiring 5.4 kWh for four hours of operation, whereas the 48 V, 50 Ah battery at an 80% depth of discharge provides a theoretical 1.92 kWh DC, or about 1.82 kWh AC assuming 95% inverter efficiency. The system has been implemented, but further measurements are required to establish a validated energy balance and quantify the reduction in PLN electricity consumption.