To address the lack of rotational inertia in power systems caused by high-penetration photovoltaic (PV) grid integration and the inherent difficulties in traditional parameter tuning, this paper proposes an optimal tuning method for frequency response parameters of PV grid-connected systems based on matrix perturbation theory (MPT). First, a small-signal state-space model of a coupled PV-thermal power system considering active power-voltage sensitivity is constructed. Second, first-order MPT is introduced to isolate the parameters to be optimized, utilizing algebraic perturbation superposition mapping instead of repeatedly solving the full-order matrix, which significantly improves computational efficiency. Finally, adaptive closed-loop tuning is implemented by combining a multi-objective optimization function with an improved sparrow search algorithm (SSA). Simulation results demonstrate that both the model and perturbation analytical maximum relative errors are within 1.2% compared to the detailed simulation benchmark. Furthermore, the proposed optimization strategy reduces the system recovery time by nearly 70% under successive load disturbances and exhibits exceptional robustness under varying irradiance levels and PV penetration rates. Balancing computational efficiency and optimization accuracy, this method provides a valuable theoretical and technical reference for the frequency stability control of renewable-dominated power grids.