The thermal management in the multiscale air-cooled data center has become a critical bottleneck limiting further development. To address this challenge, a multiscale simulation model was developed in this study to link prescribed room scale cooling conditions with chip scale CPU junction temperature. Its specific contribution is to transfer spatially varying temperature, velocity, and pressure information during the room-to-server boundary transfer and to examine the resulting internal server thermal field and CPU1/CPU2 junction-temperature responses under different cooling configurations. Under the investigated operating conditions, the simulations predict that both the computer room air conditioner (CRAC) supply temperature and velocity have significant effects on the thermal performance of the server. The CPU junction temperature shows a negative correlation with the CRAC air velocity: when the supply velocity increases from 4.5 m∙s −1 to 6.5 m s −1 , the CPU junction temperature decreases by approximately 4°C. In contrast, the CPU junction temperature is positively correlated with the supply air temperature. For the air-cooled configuration, implementing an enclosed cold aisle significantly improves airflow organization by preventing hot and cold air mixing, predicting a decrease of approximately 16°C in the CPU2 junction temperature compared with the open aisle case under the stated operating condition.