To improve the efficiency of extinguishing initial fires in the annular gaps of storage tanks, this study designs an automatic trigger carbon dioxide active fire extinguishing system. The core innovation of the system lies in the use of molten material (EVA hot-melt adhesive) to seal the spray holes, which melt upon heating during the early stage of a fire and automatically release high-pressure carbon dioxide, responding quickly. Two key engineering parameters, namely the layout of the spray holes and the installation height, were experimentally studied for their impact on fire suppression performance. The experiment found that reducing the spray height from 30cm to 20cm could significantly shorten the time to extinguish the flame, with the optimal condition (8 holes, 20cm high) taking only 15 seconds. At the same time, increasing the number of spray holes from 4 to 8 can further reduce the fire extinguishing time by 14.3% to 25%, because the porous arrangement forms a more uniform inert gas cover. Both simulations and experiments have confirmed that low-position, porous jetting enables the carbon dioxide jet to penetrate the flame plume more effectively and act directly on the combustion reaction zone, thereby maximizing its cooling and suffocation effects. This study provides direct guidance on parameter optimization for tank safety design and demonstrates the feasibility and efficiency of an active fire extinguishing device for initial annular pool fires.